BRAND NAME |
DISTRIBUTOR |
CONDUCTOR SIZE |
HALOGEN FREE |
CABLE WITHSTOOD 30 MINUTE FIRE AND SHOCK TEST |
COMMENTS |
|
None |
Helukable |
Drain wire 0.22 mm2 Incorrect |
No |
Passed |
BS 8434-2 printed on sheath is the standard for PH 120 |
|
None Sample 1 |
PKP Industrial Trading |
Drain wire 0.22 mm2 Incorrect |
No |
Failed |
|
|
None Sample 2 |
PKP Industrial Trading |
Correct |
No |
Failed |
|
|
VIONIX Fire |
View A Vision |
Correct |
Yes |
Passed |
|
|
StamnoTec |
Stanmo Cables |
Correct |
No |
Failed |
Cable sheath states PH 30 to IEC 60331. Not EN 50200 |
|
Cab-Tech Fire |
Cabcon |
Correct |
Yes |
Passed |
|
|
Kablecon |
Cabletronics |
Correct |
No |
Passed |
|
|
FR Tech |
Technoswitch |
Correct |
Yes |
Passed |
|
|
Ace Tech |
Stanmo cables |
Correct |
No |
Passed |
|
|
Ram Firecro |
Unknown |
Correct |
Yes |
Passed |
|
|
Noburn |
ADI |
Correct |
Yes |
Passed |
FDIA Cable Test Results
- Details
- Written by: Keith Norgate
- Category: Cables and Conduit
- Hits: 589